45°C inlet water lets AI halls drop chillers, in most climates

A Register column from SC26 says 45°C liquid inlets make chillers unnecessary for new AI builds. Vendors and operators say the step is smaller and chillers stay.

Figure 1. Cooling. Note: illustration generated for this story; not a chart of real data.

The short version

  • Nvidia's Rubin generation and DSX reference design accept liquid coolant at up to 45°C (113°F) and return it at about 55°C, warm enough for rooftop dry coolers to reject the heat in many climates without chillers.
  • The jump to 45°C is smaller than it looks: Blackwell systems already ran up to 40°C according to LiquidStack, and DCX says it has built GB200 deployments for 44°C.
  • DCX's CTO estimates that raising the allowed loop temperature by 10°C to 45°C could cut heat-rejection equipment spending by about one third in moderate climates such as Northern Virginia or New Jersey.
  • Chillers are unlikely to vanish from AI halls soon, because some workloads run cooler by choice, sites still host air-cooled storage and networking, and non-Nvidia or custom chips may not meet the 45°C spec.

Cooling vendors took up even more of the SC26 floor in Chicago this week than they did at SC25 in St. Louis, and a column in The Register puts it down to one number: a 45°C (113°F) liquid inlet temperature. Dan Olds writes that most liquid-cooled systems have run at 30-35°C because that was what the chips would tolerate. At 45°C, rooftop dry coolers can bring the fluid back down in almost every location, since few places see ambient temperatures near 113°F.

Olds calls chillers unnecessary for new builds. Nvidia, cooling vendors and at least one large operator agree on the direction. They disagree on how new the change is and how far it goes.

Where the 45°C figure comes from

In a June blog post, Nvidia said its newest AI servers accept coolant at up to 45°C and send it back at about 55°C, with the chips still at full performance. The coolant is 75% water and 25% propylene glycol, pumped from a CDU through cold plates in a closed loop. Nvidia describes Rubin as its first generation with 100% liquid cooling and no fans, as laid out in its DSX AI factory reference design.

The Register says Nvidia released the figure earlier this year and treats it as a large step up from 30-35°C. Other reporting points to a smaller step. At CES in January, Jensen Huang said Vera Rubin uses the same 45°C water temperature as Grace Blackwell and that a hall at that temperature needs no chiller, according to Facilities Dive. LiquidStack CEO Joe Capes told The Tech Capital that Blackwell ran inlet water up to 40°C, and DCX CTO Maciek Szadkowski said his company has GB200 deployments built for 44°C. Read together, 45°C looks like an explicit design point for Rubin and DSX, not a sudden jump.

What changes in the mechanical plant

The design The Register describes uses two closed loops. One collects heat from the IT equipment and passes it to a second loop that carries it to dry coolers on the roof. During hot spells, adiabatic assist trickles water over a mesh around the coolers to lower the effective air temperature.

The savings figures vary by source. The Register says cooling commonly takes 20-40% of facility energy in legacy designs with chillers and open evaporative towers, and that published estimates and vendor modeling put the cut in cooling energy at 50-70%, or 10-20% of total power depending on starting PUE and climate. Nvidia cites industry estimates of about 4% per degree for chiller plant temperatures and claims a 50 MW facility can save over $4 million a year in cooling energy and water by moving to liquid cooling.

On water, Nvidia says cooling towers use about 2.6 million gallons per MW per year and that its dry-cooler design brings this near zero in favorable climates. The Register puts the reduction at 80-95% in most climates.

Capital cost may be the bigger lever for builders. Szadkowski estimates that in moderate climates such as Northern Virginia or New Jersey, raising the allowed temperature by 10°C to 45°C could cut spending on heat-rejection equipment by about a third. Investors noticed: Modine, Johnson Controls and Trane each fell more than 5% after Huang’s CES remark, per The Tech Capital, though Facilities Dive reported most HVAC stocks had recovered within days.

Why chillers stay on some drawings

Nvidia itself does not claim zero chillers everywhere. Its director of data center cooling, Ali Heydari, said some climates may need them for roughly 1% of the year, and the blog contrasts the Scottish Highlands with Phoenix. Capes said chillers could still have a place in Vera Rubin halls.

Operators raise other limits. Eric Williams of Compass said hyperscale customers run some workloads cooler for performance, consistency and risk reasons, and that facilities still house storage, networking and lower-density racks. Compass designs for 80% liquid and 20% air at the facility level, with room to change the mix. The Register notes nothing public from AMD, Intel or Arm on matching 45°C, and The Tech Capital warns that custom hyperscaler chips may not meet Rubin’s spec.

Retrofits need their own checks. Pipes, pumps and heat exchangers in existing buildings may be sized for air or cooler liquid, so flow rates and pressure drops have to be verified.

What it means for new capacity

Rubin rolls out in the second half of 2026, so halls designed now will host it. The open question for each site is how much of the load will run at 45°C and how much stays on air or cooler liquid. Eliovp’s ModFlex modular facilities choose cooling per project (air, direct liquid cooling or a hybrid) and list Nvidia GB300 NVL72 and Vera Rubin among supported platforms. Liquid-cooled racks such as AMD Helios need no in-row coolers, and in-row or in-rack CDUs can be fitted when a project calls for them.

For a buyer, the practical step is to ask which chips and workloads the hall will carry, then size dry coolers for the 45°C loop and decide whether trim chiller capacity is worth keeping for the hottest hours.

Questions readers ask

Does a 45°C inlet temperature mean a data center needs no chillers at all?

In favorable climates, Nvidia says yes: dry coolers handle the heat and water use for cooling drops to near zero. In hotter places, Nvidia's Ali Heydari says chillers may still be needed for roughly 1% of the year, and LiquidStack's CEO says chillers could keep a role in Vera Rubin halls.

How much energy and water can a 45°C design save?

The Register cites published estimates and vendor modeling of 50-70% less cooling energy than a chiller-plus-tower plant, or 10-20% less total facility power, and 80-95% less water in most climates. Nvidia says cooling towers use about 2.6 million gallons per MW per year and its dry-cooler design brings that close to zero where the climate allows.

Do AMD, Intel and Arm chips support 45°C coolant?

According to The Register, none of the three has said anything public about matching 45°C, although cooling vendors say their equipment will comply. The Tech Capital also warns that custom hyperscaler chips may not be built to Rubin's spec.

Can an existing liquid-cooled hall move to 45°C?

Possibly, but it takes engineering. The Register notes that pipes, pumps and heat exchangers in existing buildings may be sized for air or cooler liquid, so flow rates and pressure drops have to be rechecked.

Sources

  1. 45°C inlets just killed the chiller. Most people haven't noticed yet, The Register
  2. Hotter Than a Hot Tub: The 45°C Breakthrough to Cool AI's Biggest Machines, NVIDIA Blog
  3. No chillers needed for Vera Rubin server racks: Nvidia CEO, Facilities Dive
  4. What does NVIDIA Rubin really mean for data centre cooling?, The Tech Capital

From Eliovp

Posts by our publisher on the same topics, republished from eliovp.com.

Nvidia confirms the modular DC direction

NVIDIA DSX POD brings Vera Rubin AI factories to modular data centers. ElioVP explains site readiness, cooling and the thinking behind ModFlex.