Spain approves data center decree with hourly 80% renewable rule

Spain's new royal decree requires data centers of 10 MW or more to match 80% of power with new renewables hour by hour, with tight PUE and water limits.

Figure 1. Policy and permits. Note: illustration generated for this story; not a chart of real data.

The short version

  • Spain's royal decree of November 20, 2026 requires data centers with at least 10 MW of grid access capacity to source 80% of their electricity from new renewable capacity, matched hour by hour.
  • Spanish data centers that take the optional phase-in, which starts at 60% renewables, must accept being among the first sites cut off when the grid is stressed.
  • Spain's interim efficiency limits for data centers are a PUE of 1.25 and a WUE of 0.1 L/kWh until the EU rating scheme is ready, which puts cooling design under direct regulatory limits.
  • Spain's data center association SpainDC plans to take the decree to court, and the People's Party has pledged to repeal it ahead of the November 29 general election.

Spain’s Council of Ministers approved a royal decree on November 20 that sets energy, environmental, resilience and data sovereignty rules for data centers. Its main requirement: any site with grid access capacity of 10 MW or more must get at least 80% of its electricity from new renewable capacity, matched hour by hour. The August draft had set the threshold at 1 MW. Sara Aagesen, Minister for Ecological Transition, announced the decree.

The government’s case is about power bills. By its estimate, unchecked data center growth would add €5 billion a year to Spanish bills: about €4 billion from higher wholesale prices as more gas is burned, and about €1 billion from higher capacity-mechanism costs. Industrial consumers would pay 25% more. Aagesen described this as a conservative scenario. The industry disputes the figure.

What counts toward the 80%

According to MACCUS, “new” means a plant connected no more than 36 months before the data center starts operating. Solar PV, some biomass and repowered plants are exceptions. On-site generation, storage and supply contracts longer than six years all count toward the share. The requirement stays in force until renewables supply more than 90% of Spain’s electricity.

For operators running around the clock, the hourly test is the hard part. Daytime solar surpluses cannot cover night hours on paper, so the night has to come from storage, wind or other contracted supply.

A phase-in that comes with curtailment

Sites can take an optional transition path that starts at 60% renewables. ARA reports steps to 70% by 2029 and 80% by 2032. MACCUS describes it as a five-year window in which a site that joins the automatic power reduction scheme, and is among the first cut off when the grid is stressed, may show 60% in peak hours until December 31, 2028, then 70% in peak and mid-peak hours. DCD reports that the decree keeps the option of power cuts or disconnection without financial compensation in some cases.

The maximum sanction is a suspension of grid access rights for up to three years. A site that falls short also pays automatic charges on its power bills in proportion to the gap, and that money goes to the capacity mechanisms. Projects already in the approval process get six months to comply, or three months if they are waiting on a grid-access tender. They can instead give up their access rights and keep their financial guarantees.

Efficiency and water limits

Sites must reach Class A under the European PUE and WUE ratings, with a water target of 0.1 L/kWh and efficiency rules adjusted for regional climate, pv magazine reports. Until the EU rating scheme and Spain’s climate-zone method are ready, MACCUS reports interim caps of PUE 1.25 and WUE 0.1. Aagesen described the water limit as almost zero use. Designs that rely on evaporative cooling will need to be checked against that cap before a site is committed.

That puts the cooling choice inside a regulatory limit from the start of design. Eliovp’s ModFlex modular facilities select cooling per project (air, direct liquid cooling, or a hybrid of both), and liquid-cooled racks such as AMD Helios need no in-row coolers. Whether a given design meets Spain’s caps depends on the site, its climate and the IT load, so it has to be worked out project by project.

Sovereignty rules apply at any size

Sites hosting public systems rated “high” under Spain’s National Security Framework must keep the most sensitive data in the European Economic Area. The operator needs staff and equipment in the EU or EEA and must control any access from outside the EEA. These rules apply regardless of the site’s capacity.

The grid pressure behind it

Data centers hold 15 GW of granted access permits in Spain, 6 GW on the transmission grid and 9 GW on distribution, which is nearly 40% of the country’s peak demand. Another 20 GW is waiting for access. Spain’s 2024 AI strategy had expected less than 4 GW of data center demand by 2030.

On the same day, the government approved a €17.14 billion grid plan to 2030 for 47.4 GW of new demand, including 9.3 GW for data centers. DCD notes that the 9.3 GW includes sites that already have transmission access and projects from the 2024 planning amendment, so it does not add to the permits already granted.

Pushback and the election

SpainDC, the data center association, says it will take the decree to court and ask for its suspension, arguing that it ignores recommendations from the competition regulator, CNMC. It says €66.9 billion of planned investment to 2030 is at risk and that data centers use 0.8% of Spain’s electricity, against 23% in Ireland. “They are not regulating our future, they are forcing us to export it,” said executive director Begoña Villacís.

The People’s Party has pledged to repeal the decree, and the general election is on November 29. For comparison, Germany’s rule reaches 100% renewables in January 2027 but is counted on balance, with no hourly test.

For anyone planning capacity in Spain, the decree turns power procurement and curtailment exposure into permit conditions. Hourly-matched supply contracts, storage and the cost of accepting priority disconnection now belong in the site model alongside the grid connection itself.

Questions readers ask

Which data centers does Spain's decree cover?

The renewable and efficiency rules apply to sites with grid access capacity of 10 MW or more. The August draft used a 1 MW threshold. The data sovereignty rules apply to sites of any size that host high-rated public systems.

What counts as new renewable capacity under the rule?

Plants connected no more than 36 months before the data center starts running, with exceptions for solar PV, some biomass and repowered plants. On-site generation, storage and supply contracts longer than six years count toward the 80% share.

Can a Spanish data center lose its grid permit for missing the target?

The maximum sanction is a suspension of grid access rights of up to three years, plus automatic charges on power bills in proportion to the shortfall. Sites can also be curtailed or disconnected during grid stress, in some cases without compensation.

How does Spain's rule compare with Germany's?

Germany has required 50% renewables for data centers since January 2024 and will require 100% from January 2027, but counts it on balance with no hourly test. Spain's 80% share must be matched hour by hour.

Sources

  1. Spain approves decree on data centers to curb electricity costs, DCD
  2. Spain approves new data center rules requiring 80% renewable electricity, pv magazine Global
  3. The Spanish government approves the data center decree to prevent a €5 billion "impact" on the electricity bill, ARA in English
  4. Spain will make big data centers prove 80% green power, hour by hour, MACCUS