Ecolab and CoolIT launch a 3 MW coolant distribution unit for AI racks
Ecolab's CoolIT CHx 3000 CDU is rated at 3 MW, runs on 45 C water, and ships from Q1 2027. It is aimed at racks of 190 kW and up.
The short version
- Ecolab unveiled the CoolIT CHx 3000 on 16 November 2026, a coolant distribution unit rated at 3 MW of cooling at a 3 C approach temperature.
- The unit supports 45 C warm-water operation and is aimed at racks around 190 kW for platforms such as Nvidia Vera Rubin, with shipments starting in Q1 2027.
- The reported claim of 18 racks at 190 kW per unit adds up to 3.42 MW, above the 3 MW rating, so the figures need checking against the final datasheet.
Ecolab has launched a new coolant distribution unit (CDU) for liquid-cooled AI data centers, the CoolIT CHx 3000, rated at 3 MW. The company announced it on 16 November at the SC26 supercomputing conference in Chicago, and DatacenterDynamics covered the details on 18 November.
What the unit does
The CHx 3000 is a liquid-to-liquid CDU for rows or whole facilities. DatacenterDynamics reports that it delivers 3 MW of cooling at a 3 C (37.4 F) approach temperature difference, and that its dual heat exchangers support warm-water operation at 45 C (113 F). It draws 75 kW itself. Ecolab says it is CoolIT’s highest-capacity CDU so far.
The unit includes Ecolab’s 3D TRASAR monitoring, which tracks the condition of the coolant loop that serves the IT equipment: temperature, differential pressure, pH, conductivity, turbidity, flow rate and glycol concentration. Ecolab calls this the first smart thermal management system for direct liquid cooling, which is the company’s own description. Alfa Laval is supplying heat exchanger and flow components. Ecolab acquired CoolIT earlier this year, according to DatacenterDynamics, and this week also announced a partnership with Siemens to combine its cooling technology with Siemens’ power distribution, automation and digital twin software.
Units are expected to ship from the first quarter of 2027.
The rack numbers
DatacenterDynamics reports that CoolIT says the CHx 3000 can cool up to 18 racks per CDU at 190 kW each, enough for hardware such as Nvidia Vera Rubin GPUs. Those two figures multiply to 3.42 MW, which is more than the 3 MW rating. That is our arithmetic. Either the claim is a peak case, or the rack count or the per-rack power is approximate. We could not find a datasheet that settles it, and the press release does not state a rack count.
For comparison, NVIDIA’s DGX GB200 guide puts a full rack at approximately 120 kW, with liquid cooling on the CPUs and GPUs and air cooling for networking and storage. A 190 kW rack is about 58 percent higher (our calculation from those two numbers). It is the density where air cooling stops being a design option.
What it means for planners
Three specifications are worth checking when a CDU is on the shortlist.
The first is the approach temperature. A 3 C approach means the facility water can be close to the coolant temperature, and the unit’s 45 C rating means it is built to run with warm facility water. How much chiller energy that saves depends on the site’s climate, and neither source gives a figure.
The second is monitoring. A leak or a fouled coolant loop on one CDU affects every rack it serves, so continuous coolant measurement is a reasonable thing to ask vendors for.
The third is block size. One 3 MW unit sets a natural increment for cooling and IT load, and it fits designs that add capacity in blocks of a few megawatts.
On the facility side, Eliovp’s ModFlex modular buildings choose cooling per project: air, direct liquid cooling or a hybrid of both. Eliovp lists AMD Instinct MI355X, NVIDIA B300 and NVIDIA GB300 NVL72 as target platforms, with an example of 16 GB300 NVL72 racks at 150 kW each, or 2.4 MW of IT load. See eliovp.com and Eliovp’s post on 1 to 2 MW NVL modules.
Questions readers ask
What is a coolant distribution unit (CDU)?
A CDU moves heat between the liquid loop that serves the servers and the facility's water loop. In direct liquid cooling, it holds the coolant, pumps it to cold plates on the chips and returns the heat to the building.
How much power does an NVIDIA GB200 rack use?
NVIDIA's DGX GB200 user guide gives the rack power as approximately 120 kW. The CoolIT unit is aimed at higher-density racks, about 190 kW per rack according to DatacenterDynamics.
When can the CoolIT CHx 3000 be bought?
DatacenterDynamics reports that units will ship beginning in the first quarter of 2027.