Vertiv extends its 800 VDC power line to the compute pod and the data hall

Vertiv added a 1.5 MW pod power center, an 800 VDC battery cabinet and a 5 MW solid-state transformer to its 800 VDC line. What it means for builders.

Figure 1. Power and grid. Note: illustration generated for this story; not a chart of real data.

The short version

  • Vertiv's 800 VDC portfolio now spans three levels: a sidecar power rack for individual IT racks, a 1.5 MW power center for a row or pod, and a 5 MW medium-voltage solid-state transformer for the data hall.
  • The new equipment is in pilots, technical validation and joint development with customers, and Vertiv has not given a shipping date.
  • Vertiv's PowerNexus MV SST converts medium-voltage AC to 800 VDC in one stage, but fault ride-through and power smoothing need separate energy storage on the DC bus.
  • Vertiv expects AC and DC distribution to coexist, with brownfield sites, colocation halls and new AI campuses each likely to adopt 800 VDC at a different level.

Vertiv has added compute pod and data hall systems to its 800 VDC power portfolio. The company announced the products in mid-November and showed them at SC26 (Nov. 17 to 22, 2026). The line began with the PowerDirect 5000 Power Rack in May 2026 and now covers three levels: the rack, the compute pod and the data hall. Vertiv says the portfolio handles power conversion, energy storage, distribution and protection all the way from the medium-voltage grid to the compute tray.

There is no shipping date. Vertiv says pilot programs, technical validation and joint development with customers are underway.

Rack level: a sidecar for existing halls

The PowerDirect 5000 sits next to the IT rack and can be configured up to 800 kW. It takes facility 480 VAC and puts out either 800 VDC or ±400 VDC. Inside are 30 hot-pluggable 30 kW power supply units and a battery backup unit designed for at least 50 seconds of hold-up. One power rack feeds one or two IT racks.

In the IT rack itself, the PowerDirect 3000 shelf (90 kW, 19-inch, 1U) steps 800 VDC down to 54 VDC for the compute trays at up to 98.5% peak efficiency. It supports 180% pulse power for 0.5 milliseconds.

Vertiv says taking conversion and storage out of the IT rack frees 8 to 16 rack units. Upstream AC gear stays where it is, and moving between 800 VDC and ±400 VDC needs only small hardware configuration changes. The target is brownfield sites, retrofits and halls running both AC and DC.

Compute pod level: one converter per row

The PowerDirect 9000 Power Center is a 1.5 MW unit that converts 480 VAC to 800 VDC for a whole row or pod. It feeds the PowerBar Track DC busway and tap-off boxes, which in turn supply the PowerDirect 3000 shelves in each rack. Capacity grows in 60 kW steps across 27 hot-pluggable power supplies.

Backup comes from the EnergyCore Li5 battery cabinet, which connects straight to the DC bus. Each cabinet provides 200 kW of continuous backup at up to 98% conversion efficiency, and up to six can run in parallel with active current sharing.

With conversion done once ahead of the row, each IT rack no longer needs its own power rack. The pod design also handles mixed AC and DC loads, and Vertiv is aiming it at colocation providers whose tenants run different workloads and GPU generations.

Data hall level: a 5 MW solid-state transformer

The PowerNexus MV SST converts medium-voltage AC to 800 VDC in a single stage and feeds Vertiv’s DC busway. Vertiv says this removes two to three intermediate conversion steps, and the unit provides galvanic isolation. It is an outdoor, liquid-cooled, containerized unit rated at up to 98% AC-to-DC efficiency. One SST supports Vertiv’s 4.8 MW “super pod” reference architecture without chaining units together.

Power can flow in both directions, which Vertiv says improves grid power quality and allows active power support. Fault ride-through and power smoothing are not built in: they need external energy storage tied to the 800 VDC bus through a DC/DC converter.

Vertiv pitches the SST at campus-scale, purpose-built AI factories. Moving conversion outdoors frees indoor floor space for compute, and the containerized format is meant to make repeat builds across a campus simpler.

On safety, the portfolio uses touch-proof busbars, high-voltage isolation, midpoint grounding, ground-fault detection and arc-flash prevention, with Vertiv service offerings built for DC environments.

What it means for builders

Vertiv does not claim the industry will switch all at once. It says operators are evaluating 800 VDC as a route to higher density, that adoption will not follow one architecture or timeline, and that AC and DC will coexist. Chief Product and Technology Officer Scott Armul described the 800 VDC power train as “a set of architectures and system designs.”

In practice the three levels line up with three kinds of project. An operator retrofitting an existing hall can add sidecar power racks and keep its 480 VAC distribution. A colocation provider with mixed tenants can put one power center at the head of a row and run DC busway down it. A team planning a new campus can design around the medium-voltage SST, but has to plan for outdoor pads, liquid cooling for the transformer units and separate storage on the DC bus for ride-through.

The choice also moves batteries and conversion gear around the site. At rack level they sit beside the IT racks. At pod level they sit at the end of the row. At hall level conversion moves outdoors. Each layout changes how much white space is left for compute and where maintenance staff need DC safety training.

Builders who add capacity in stages will want the power train’s step size to fit their build blocks. Eliovp’s ModFlex modular facilities, for example, cover the building, power and cooling, are designed around what the IT equipment needs, and add capacity module by module. Modules are sized per project; the published example is 16 GB300 NVL72 racks at 150 kW each, or 2.4 MW of IT load.

With the new Vertiv systems still in pilots, teams planning halls on near-term schedules should treat 800 VDC as an option to design room for, and confirm availability with Vertiv before committing a power architecture.

Questions readers ask

What did Vertiv add to its 800 VDC portfolio?

At the compute pod level it added the 1.5 MW PowerDirect 9000 Power Center and the EnergyCore Li5 800 VDC battery cabinet. At the data hall level it added the PowerNexus MV SST, a 5 MW solid-state transformer that converts medium-voltage AC to 800 VDC. These join the PowerDirect 5000 Power Rack and the PowerDirect 3000 power shelf at rack level.

Can operators buy the new systems now?

Vertiv says pilot programs, technical validation and joint development work with customers are underway. Its release does not give a shipping date.

Does 800 VDC require replacing existing AC equipment?

Not at rack level. Vertiv says the PowerDirect 5000 takes facility 480 VAC, so upstream AC equipment can stay in place, and it pitches this option at brownfield sites, retrofits and mixed AC/DC facilities.

How much rack space does moving power out of the IT rack save?

Vertiv says moving conversion and energy storage out of the IT rack frees 8 to 16 rack units.

Sources

  1. Vertiv advances 800 VDC power architectures to support growing AI data center demands, Vertiv
  2. Vertiv Adds 5 MW 800 VDC System for AI Data Halls (/U P D A T E/ - Vertiv Holdings Co/), Stock Titan
  3. Vertiv expands 800VDC power portfolio for AI data center market, DCD (DatacenterDynamics)

From Eliovp

Posts by our publisher on the same topics, republished from eliovp.com.

Nvidia confirms the modular DC direction

NVIDIA DSX POD brings Vera Rubin AI factories to modular data centers. ElioVP explains site readiness, cooling and the thinking behind ModFlex.